create 관리자access_time 2024.10.30 13:38visibility 11assignment EBOP(Electrical Balance of Plant) & ESS(Energy Storage System) System
Purpose : Battery for ESS system
Equipment configuration : cell, module, rack, BPU
Cell : 16 Wh(95%), 1S1P
Module : 4.54 kWh(65V DC), 18S18P
Rack(11 modules) : 50 kWh x 3EA, 18S18P
Charge-discharge voltage : 620 ~ 812 V DC(Nominal 715V DC)
Charge-discharge current : 34.96A
BPU(Battery Protection Unit) with rack BMS
- DC contactor(2EA) : 900V DC / 100A DC
-DC fuse(2EA) : 1000V DC / 100A DC