create 관리자access_time 2024.10.30 13:39visibility 11assignment EBOP(Electrical Balance of Plant) & ESS(Energy Storage System) System
PCS(Power Conversion System)
Capacity : 500kW
Voltage/Current/Frequency : 3-phase, 4-wire 350/220V / 760A / 60Hz
Operation mode : charge, discharge, stop, active standby
Battery min./max. voltage tolerance : 550V DC / 850V DC
PMS(Power Management System)
- Real time monitoring for ESS
- Settings for ESS charge-discharge, PCS output, temperature and humidity